←
Valve Authority Explorer SIZE IT · SPLIT THE ΔP · WATCH THE INSTALLED CURVE COLLAPSE

1 · The circuit (at design flow)

2 · The valve you bought

0.50VALVE AUTHORITY N
N = ΔPvalve ÷ ΔPtotal  (at design flow)
ΔP ACROSS VALVE
REQUIRED Cv / Kv
TRAVEL AT DESIGN
TRAVEL AT MIN FLOW
OVERSIZE FACTOR
INSTALLED GAIN @ DESIGN

Reading the curves. The dashed grey line is the inherent characteristic — what the trim does on a test bench at constant ΔP. The solid steel line is the installed characteristic — the same trim inside this circuit, where opening the valve raises the flow, the system loss grows as Q², and the valve's own ΔP collapses. Low authority bends the installed line up into a quick-opening shape: all the flow change happens in the first 20 % of travel, and the loop has almost no resolution left anywhere above it.

Not modelled: choked flow and flashing. Liquid flow stops obeying Q = Kv√(ΔP/SG) once ΔP exceeds ΔPchoked = FL²(P₁ − FF·Pv); past that point more ΔP buys no more flow, only cavitation damage. A pump-curve droop (head falling as flow rises) is also ignored — ΔPtotal is held constant here.

Educational teaching tool — simplified and illustrative. Not for engineering design use.